Smoke extraction line for individual sections according to EN12101-7 made of galvanized steel sheet tested according to EN1366-9. The
smoke removal duct is tested at room temperature with 1500 Pa vacuum and at 600 ° C with 500 Pa negative pressure to
a time of 120 minutes.